Guide

Overcurrent Relay Setting Checklist

A step-by-step checklist for setting a phase and earth-fault overcurrent relay on a transformer feeder: data, CT check, pickup, curve, grading, high-set, testing.

Updated 2026-10-07

Protection and MVFree, no sign-upWorked examples

This checklist covers the main steps in setting a phase and earth-fault IDMT overcurrent relay on a distribution transformer feeder, with one worked example. It is a general method. Your utility’s rules, the relay manufacturer’s manual and the project specification take precedence over anything here, and setting values quoted as common practice are starting points, not requirements.

Use the browser’s print function to get a clean copy of the checklist.

1. Collect the data

2. Check the CT

3. Set the phase pickup

4. Choose the curve and TMS

5. Set the high-set (instantaneous) element

6. Set the earth-fault protection

7. Verify and document

Worked example

A 1,000 kVA, 11 kV / 400 V transformer with 5 % impedance is protected on the 11 kV side by an IDMT relay on a 100/1 A CT.

Full-load current. On the 11 kV side, 1,000,000 / (1.732 × 11,000) = 52.5 A, from the transformer full-load current calculator.

Pickup. 1.2 × 52.5 = 63 A. On a 100 A CT that is 0.63 A of relay setting. Rounded to the next available step in this example, 65 A.

Through-fault. With an infinite-bus source, a three-phase fault on the 400 V side gives 1,443 A / 0.05 = 28.9 kA at 400 V, which appears on the 11 kV side as 52.5 / 0.05 = 1,050 A, from the short-circuit current calculator.

Curve and TMS. On a standard inverse curve with TMS 0.1, the operating time at 1,050 A is 0.1 × 0.14 / ((1,050 / 65)0.02 − 1) = 0.245 s. This is the time the 11 kV relay takes to trip for a fault on the 400 V side. The LV protection must clear that fault at least one grading margin sooner, so with a 0.3 s margin it would need to operate in less than 0 s, which is impossible: with these settings the relay does not discriminate with an LV device on this fault. The fix is to raise the TMS until the 11 kV relay’s time at 1,050 A exceeds the LV device’s clearing time plus the margin, then recheck the time at the minimum fault current. For example, TMS 0.3 gives 0.73 s at 1,050 A, which leaves 0.43 s for the LV device to clear the fault with a 0.3 s margin to spare. This is the normal back-and-forth in grading, and it is why the checklist has you test both fault levels.

High-set. 1.3 × 1,050 = 1,365 A, which is also above the inrush of 8 to 12 times full-load current (420 to 630 A), so the instantaneous element can be set at about 1,400 A without tripping on energization.

Check. A clearing time of a fraction of a second is well inside the 2 s short-circuit duration that IEC 60076-5 uses as its basis for transformer withstand, but confirm the rating on the manufacturer’s data sheet for your own unit.

Common mistakes

Related calculators